5 voltage drop, 6wiring, 3 preparing for operation – Pilz PDP67 F 4 code User Manual
Page 24
![background image](https://www.manualsdir.com/files/762776/content/doc024.png)
6.3
Preparing for operation
6
Wiring
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-8
Connection example 2: Series connection for connecting three sen-
sors (X1 ... X3) to the first module
*Adapter:
PDP67 Connector cs/PDP67 Connector csVA
6.3.1.5
Voltage drop
Voltage drop
6-
Verdrahtung_PNOZ ml2p_Leitungslänge-Spannungsabfall
The max. cable length depends on the voltage drop in the supply voltage
cables. The level of voltage drop is determined by the:
Cable resistance on the supply voltage cables
Operating current of the modules
Load on the modules
To increase the max. cable length, the input voltage can be permanently
increased by the voltage tolerance (see Technical Details).
*