Assignment of female connectors, 6wiring, 2 assignment of female connectors – Pilz PDP67 F 4 code User Manual
Page 18
![background image](https://www.manualsdir.com/files/762776/content/doc018.png)
6.2
Assignment of female connectors
6
Wiring
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-2
6.2
Assignment of female connectors
6200
Assignment of female connectors
6-
Anschluss_PDP_PSEN_Schnittstellenbelegung
Inputs/outputs
X1 to X4
Layout
8-pin M12 female connectors for con-
necting the sensors
1: input I2 (S21)
2: 24 V DC (A1)
3: Output O1 (12)
4: Output O2 (22)
5: Signal output (Y32)
6. Input I1 (S11)
7. 0 V (A2)
8. input for control command for mag-
netic guard locking (S31)
Inputs/outputs
X5
Layout
8-pin M12 female connector for con-
necting to the safety inputs of an eval-
uation device
1: Input I2
2: 24 VDC
3: n.c.
4: n.c.
5: n.c.
6. Input I1
7. 0 V
8. n.c.
2
1
7
6
8
5
4
3
2
1
7
6
8
5
4
3