8 technical details, Section 8, Technical details – Pilz PSSu E F PS2 User Manual
Page 26: 8technical details

Technical details
Operating Manual PSSu E F PS2(T)(R)
1002237EN03
26
8
Technical details
General
312192
314192
315192
Approvals
CE
CE
CE
Application range
Standard/failsafe
Standard/failsafe
Standard/failsafe
Module's device code
0803h
0803h
0803h
Application in system en
vironment B
From FS firmware ver
sion, head modules
1.3.0
1.3.0
1.5.0
From ST firmware ver
sion, head modules
1.3.0
1.3.0
1.5.0
Electrical data
312192
314192
315192
Supply voltage
for
Module supply
Module supply
Module supply
Voltage
24 V
24 V
24 V
Kind
DC
DC
DC
Kind
DC
DC
DC
Voltage tolerance
30 %/+25 %
30 %/+25 %
30 %/+25 %
Current load capacity
at UB
0,5 A
0,5 A
0,5 A
Inrush current that the
external power supply
must provide
4,0 A
4,0 A
4,0 A
Output of external
power supply (DC)
7,0 W
7,0 W
7,0 W
Supply voltage
for
Periphery supply
Periphery supply
Periphery supply
Voltage
24 V
24 V
24 V
Kind
DC
DC
DC
Voltage tolerance
30 %/+25 %
30 %/+25 %
30 %/+25 %
Current load capacity
at UB
10,0 A
10,0 A
10,0 A
Rated surge voltage
3050 V
3050 V
–
Potential isolation
between module supply
and periphery supply
3050 V
3050 V
3050 V