beautypg.com

8 technical details, Section 8, Technical details – Pilz PSSu E F PS2 User Manual

Page 26: 8technical details

background image

Technical details

Operating Manual PSSu E F PS2(­T)(­R)
1002237­EN­03

26

8

Technical details

General

312192

314192

315192

Approvals

CE

CE

CE

Application range

Standard/failsafe

Standard/failsafe

Standard/failsafe

Module's device code

0803h

0803h

0803h

Application in system en­
vironment B

From FS firmware ver­
sion, head modules

1.3.0

1.3.0

1.5.0

From ST firmware ver­
sion, head modules

1.3.0

1.3.0

1.5.0

Electrical data

312192

314192

315192

Supply voltage

for

Module supply

Module supply

Module supply

Voltage

24 V

24 V

24 V

Kind

DC

DC

DC

Kind

DC

DC

DC

Voltage tolerance

­30 %/+25 %

­30 %/+25 %

­30 %/+25 %

Current load capacity
at UB

0,5 A

0,5 A

0,5 A

Inrush current that the
external power supply
must provide

4,0 A

4,0 A

4,0 A

Output of external
power supply (DC)

7,0 W

7,0 W

7,0 W

Supply voltage

for

Periphery supply

Periphery supply

Periphery supply

Voltage

24 V

24 V

24 V

Kind

DC

DC

DC

Voltage tolerance

­30 %/+25 %

­30 %/+25 %

­30 %/+25 %

Current load capacity
at UB

10,0 A

10,0 A

10,0 A

Rated surge voltage

3050 V

3050 V

Potential isolation
between module supply
and periphery supply

3050 V

3050 V

3050 V

This manual is related to the following products: