7 operation, 1 messages, 2 display elements – Pilz PSSu E F PS2 User Manual
Page 24: Section 7, Operation, Messages, Display elements, 7operation

Operation
Operating Manual PSSu E F PS2(T)(R)
1002237EN03
24
7
Operation
7.1
Messages
A module error is displayed via the "Err" LED, signalled to the head module and then
entered in the head module's diagnostic log.
The module can detect the following errors:
Module error
Explanation
Remedy
Startup error
Error as the PSSu system starts
up
Change faulty module.
Configuration error
Incorrect module type configured.
The configured hardware registry
does not match the actual hard
ware registry.
FS communication error
Error during FS communication
Change faulty module.
Temperature error: too warm
Ambient temperature too high:
Entry in the error stack or dia
gnostic log
Ensure there is sufficient ventila
tion in the control cabinet or pre
vent overload.
Overvoltage error
A system voltage or infeed is too
high.
Stabilise the supply or change the
faulty supply voltage module.
Undervoltage error
A system voltage or infeed is too
low.
Stabilise the supply or change the
faulty supply voltage module.
Error in the overvoltage protection
diodes
Overvoltage protection diodes are
defective.
Change faulty supply voltage mod
ule.
Further information on PSSu error messages is available in the online help for PSS WIN
PRO or PAS4000.
7.2
Display elements
Legend:
LED on
LED flashes
LED off