On base modules with screw terminals:
–
If you use a multistrand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm
2
, Form A or C,
although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 609471, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.
–
Maximum torque setting: 0.8 Nm
}
Use copper wiring.
6.2
Terminal configuration
}
For use as a supply module to refresh the module supply and periphery supply
}
For use as a supply module to form supply groups
–
To interrupt the incoming periphery supply and Crail
–
To provide subsequent modules with the module supply, periphery supply and C
rail supply
Base module
Terminal configuration
Screw terminals:
PSSu BSR 2/8S
PSSu BSR 2/8ST
Cage clamp terminals:
PSSu BSR 2/8C
PSSu BSR 2/8CT
11: +24 V infeed for module
supply,
interrupted to the left
21: 0 V infeed for module
supply
12 22: 0 V Periphery Sup
ply,
interrupted to the left
(1222 linked within the base
module)
13 23: +24 V periphery sup
ply, interrupted to the left
(1323 linked within the base
module)
1424 Crail supply,
interrupted to the left
(1424 linked within the base
module)