beautypg.com

2 integrated protection mechanisms, 2 configuration, 1 converter characteristics/default value – Pilz PSSu E F AI I User Manual

Page 14: Integrated protection mechanisms, Configuration, Converter characteristics/default value

background image

Function description

Operating Manual PSSu E F AI I(­T)(­R)
21981­EN­05

14

WARNING!

Limit values selected in the user program too low or too high!

Risk of serious injury and death!

– Take into account the max. safety­related accuracy when defining

the limit values in the user program.

}

For safe resolution up to 256 levels you will need to use two analogue inputs and to
carry out a feasibility test.

}

With 2­channel mode, the achievable safety­related accuracy will depend on the mod­
ule's measuring accuracy and sensors.

}

The module's measuring accuracy is calculated by adding all deviations from the meas­
uring range limit value (see chapter entitled "Technical Details"). With 2­channel, di­
verse operation, this value is doubled in the worst case.

Illustration of the resolution ranges:

2 4 8 16 32 64 128 256 512 1024 2048 4096

0 1 2 3 4 5 6 7 8 9 10 11

Bit

Resolution

Safe (1 analogue input)

Safe (2 analogue inputs)

Standard

MSB

LSB

4.1.2

Integrated protection mechanisms

When the PSSu E F PS1(­T) is used to supply the system, the module supply is buffered
for 20 ms if the supply voltage is interrupted.

The module detects the following errors:

}

Start­up error

}

Configuration error

}

FS communication error

}

Bus termination error

4.2

Configuration

4.2.1

Converter characteristics/default value

The table below shows the converted data formats of the analogue input currents. When
the digital values are converted into I/O data elements, the three highest binary digits are
filled with "0".