beautypg.com

2 terminal configuration, Terminal configuration – Pilz PSSu E F 2DO 2 User Manual

Page 25

background image

Wiring

Operating Manual PSSu E F 2DO 2(­T)(­R)
21322­EN­05

25

}

On base modules with screw terminals:

If you use a multi­strand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm

2

, Form A or C,

although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 60947­1, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.

Maximum torque setting: 0.8 Nm

}

Use copper wiring.

6.2

Terminal configuration

Base module

Terminal configuration

Screw terminals:
PSSu BP 1/8S
PSSu BP 1/8S­T

Cage clamp terminals:
PSSu BP 1/8C
PSSu BP 1/8C­T

Without C­rail:

11: Output O0

21: Output O1

12­22: 0 V periphery supply
(12­22 linked within the base
module)

13­23: 0 V periphery supply
(13­23 linked within the base
module)

14: Not connected

24: Not connected

21

11

22

12

23

13

24

14

This manual is related to the following products: