beautypg.com

Display elements for devicenet diagnostics, 7operation, 2 display elements – Pilz PSSu H DN User Manual

Page 25: 2 display elements for devicenet diagnostics, The module has been removed

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-3

7.2

Display elements

7

Operation

Remedy: Correct the hardware registry.

2. Error: A module is missing. Possible cause:

The module has been removed.

The module has an error and is no longer registering after a reset.

The module has an error and switches to a system stop.

The module no longer has a voltage supply.

Remedy: Rectify the above points.

7.2.2

Display elements for DeviceNET diagnostics

Display elements for DeviceNET diagnostics

7-

][BA_Anzeige DN

The module has LEDs to display various DeviceNet states (“MNS” LED

and “I/O” LED).

Die “MNS” LED indicates the status of the DeviceNet interface and the

network status:

LED for DeviceNet diagnostics

Key

MNS

Colour

Status

- - -

No bus connection because
- there is no voltage or
- DUP-MAC-ID test is not com-
plete.

Green

“Operational and Online, Con-
nected” status

“Operational and Online, Not Con-
nected” status

Red

Recoverable fault (“Minor Fault” or
“Connection Time-out”)

Non-recoverable fault (“Critical
Fault” or “Critical Link Fault”)

Red/
green

Communication error: Error due to
bus access (“Identity Communi-
cation Faulted Request”)

DeviceNet

Usb Dev

SB

I/O

SB ADDRESS

USB

2

D -

3

D +

5

G N D

USB

0

3

6

9

x 10

0

3

6

9

x 1

MNS

I/O

ADDRESS

OFF ON

S2

S1

32

16

8

4

2

1

- -

BAUD

S2

BAUD

125K

OFF

250K

OFF

500K

OFF

- -

ON

S1OFFON ON ON

MNS

This manual is related to the following products: