Devicenet, Connection to devicenet, Selector switch for setting the transmission rate – Pilz PSSu H DN User Manual
Page 16: 4function description, 2 devicenet, 1 connection to devicenet

4.2
DeviceNET
4
Function description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-2
4.2
DeviceNET
4200
DeviceNET
4-
4.2.1
Connection to DeviceNet
Connection to DeviceNet
4-
][Funktionsbeschreibung_BA_Zusatz DN Kopplung
A PSSu system with DeviceNet interface operates as a DeviceNet Slave
on DeviceNet (Group 2 Only Device). The interface supports the ex-
change of polled I/O messages. This must be taken into account on the
master module settings. The specifications of the Open DeviceNet Ven-
dor Association (ODVA) apply for a PSSu.
4.2.2
Selector switch for setting the transmission rate
Selector switch for setting the transmission rate
4-
][Funktionsbeschreibung_BA_Zusatz DN bertragung
The transmission rate of a PSSu is set via the “BAUD” DIP switches S1
and S2.
“BAUD” DIP switch
Key
Example:
Switch designation
125
kBit/s
250
kBit/s
500
kBit/s
- - -
Transmission rate
250 kBit/s
- -
Not connected
S2
OFF
OFF
ON
ON
S1
OFF
ON
OFF
ON
32
Station address
16
8
4
2
1
INFORMATION
The transmission rate should only be set when the module is
switched off (no voltage applied).
The settings are only transferred when booting. Any changes
made to the settings during operation will not be transferred.
ADDRESS
OFF ON
S2
S1
32
16
8
4
2
1
- -
BAUD