Selector switch for setting the station address, 4function description, 2 profibus – Pilz PSSu H DP User Manual
Page 17: 2 selector switch for setting the station address

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-3
4.2
PROFIBUS
4
Function description
4.2.2
Selector switch for setting the station address
Selector switch for setting the station address
4-
][Funktionsbeschreibung_BA_Zusatz DP Station
The station address of a PSSu is set via the “ADDRESS” DIP switch. The
DIP switch is binary coded. Permitted station addresses are in the range
0
D
... 125
D
.
If station address 126
D
is set via the DIP switch, the address can be as-
signed via the Master. The Set Slave Address command (SSA) must be
run for this purpose.
The station address is set as follows:
DIP switch “ADDRESS”
Key
Example:
Switch designation
OFF
ON
Station address 52
D
- -
Not connected
- -
64
0
64
D
32
0
32
D
16
0
16
D
8
0
8
D
4
0
4
D
2
0
2
D
1
0
1
D
INFORMATION
The station address should only be set when the module is
switched off (no voltage applied).
The settings are only transferred when booting. Any changes
made to the settings during operation will not be transferred.
ADDRESS
OFF ON
- -
64
32
16
8
4
2
1
- -