4.2
PROFIBUS
4
Function description
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-2
4.2
PROFIBUS
4200
PROFIBUS
4-
4.2.1
Connection to PROFIBUS DP
Connection to PROFIBUS DP
4-
][Funktionsbeschreibung_BA_Zusatz DP Kopplung
The PSSu system with PROFIBUS interface is a passive PROFIBUS DP
subscriber (Slave). The basic functions of communication with
PROFIBUS DP correspond to EN 50170.
The specifications of the PROFIBUS User Group (PNO) apply for a
PSSu.
The data length of the output data may be a max. of 1536 Bytes because
the memory of the PROFIBUS protocol chips is 1.5 kByte. The max. data
length is calculated as:
3 x length of the input data
+ 3 x length of the output data
+ 2 x length of the diagnostic data
+ 4 x length of the configuration data
+ 64 Byte