1 safety characteristic data, Safety characteristic data – Pilz PSSu H PLC1 FS SN SD User Manual
Page 40
Technical Details
Operating Manual PSSu H PLC1 FS SN SD(T)(R)
21939EN10
40
9.1
Safety characteristic data
Operating
mode
EN ISO
138491:
2008
PL
EN ISO
138491:
2008
Category
EN IEC
62061
SIL CL
EN IEC
62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
138491:
2008
T
M
[year]
–
PL e
Cat. 4
SIL CL 3
4,14E09
SIL 3
3,51E05
20
If the module is operated at an ambient temperature above 60° C, the values stated in the
table for PFH
D
and PFD will need to be doubled when a safety function is calculated.
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.