beautypg.com

1 safety characteristic data, Safety characteristic data – Pilz PSSu H PLC1 FS SN SD User Manual

Page 40

background image

Technical Details

Operating Manual PSSu H PLC1 FS SN SD(­T)(­R)
21939­EN­10

40

9.1

Safety characteristic data

Operating
mode

EN ISO
13849­1:
2008

PL

EN ISO
13849­1:
2008

Category

EN IEC
62061

SIL CL

EN IEC
62061

PFH

D

 [1/h]

IEC 61511

SIL

IEC 61511

PFD

EN ISO
13849­1:
2008

T

M

 [year]

PL e

Cat. 4

SIL CL 3

4,14E­09

SIL 3

3,51E­05

20

If the module is operated at an ambient temperature above 60° C, the values stated in the
table for PFH

D

 and PFD will need to be doubled when a safety function is calculated.

All the units used within a safety function must be considered when calculating the safety
characteristic data.

INFORMATION

A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.