Pilz PSSu H PLC1 FS SN SD User Manual
Page 38
Technical Details
Operating Manual PSSu H PLC1 FS SN SD(T)(R)
21939EN10
38
Environmental data
312070
314070
315070
Ambient temperature
In accordance with the
standard
–
–
EN 50155
Temperature range
0 60 °C
40 70 °C
40 70 °C
In accordance with the
standard
–
–
EN 501251
Temperature range
–
–
40 ... +70 °C
In accordance with the
standard
–
–
EN 501253
Temperature range
–
–
40 ... +70 °C
Storage temperature
Temperature range
25 70 °C
40 70 °C
–
Climatic suitability
In accordance with the
standard
EN 60068278
EN 60068230, EN
60068278
–
Humidity
93 % r. h. at 40 °C
93 % r. h. at 40 °C
–
Condensation during op
eration
Not permitted
Shortterm
–
EMC
EN 6100042, EN
6100043, EN 6100044,
EN 6100045, EN
6100046, EN 6100062,
EN 6100064
EN 6100042, EN
6100043, EN 6100044,
EN 6100045, EN
6100046, EN 6100062,
EN 6100064
EN 6100042, EN
6100043, EN 6100044,
EN 6100045, EN
6100046, EN 6100062,
EN 6100064
Vibration
In accordance with the
standard
EN 6006826
EN 6006826
EN 501253
Frequency
10,0 55,0 Hz
10,0 55,0 Hz
5,0 2000,0 Hz
Amplitude
0,35 mm
0,35 mm
–
Acceleration
1g
1g
0,23 g
Broadband noise
In accordance with the
standard
–
EN 60068264
EN 61373
Frequency
–
5 500 Hz
5 150 Hz
Acceleration
–
1,9grms
0,79 g RMS
Shock stress
In accordance with the
standard
EN 60068227
EN 60068227
EN 501253
Acceleration
15g
15g
2g
Duration
11 ms
11 ms
11 ms
In accordance with the
standard
EN 60068229
EN 60068229
EN 61373
Acceleration
10g
10g
5g
Duration
16 ms
16 ms
30 ms
Supply interruptions
In accordance with the
standard
–
–
EN 50155
Class
–
–
S2, C1, C2