Pilz PSSu H PLC1 FS SN SD User Manual
Page 37
Technical Details
Operating Manual PSSu H PLC1 FS SN SD(T)(R)
21939EN10
37
External communication 312070
314070
315070
EtherNet/IP Adapter
Cycle time (tExtCom)
4...655 000 ms
4...655 000 ms
4...655 000 ms
Manufacturer’s ID
181
181
181
Product ID
1
1
1
EDS file
00B5000C00010100.eds 00B5000C00010100.eds 00B5000C00010100.eds
Unit type
Adapter
Adapter
Adapter
Cycle time (RPI)
4...655 000 ms
4...655 000 ms
4...655 000 ms
Maximum data length
508 Byte
508 Byte
508 Byte
Maximum number of I/
O connections
1
1
1
Raw UDP
Memory size
8 Kbyte
8 Kbyte
8 Kbyte
Cycle time (t_ExtCo)
2...2 000 000 ms
2...2 000 000 ms
2...2 000 000 ms
SafetyNET p interface
312070
314070
315070
Number
2
2
2
IP address (automatically
off)
169.254.X.Y
169.254.X.Y
169.254.X.Y
Connection
RJ45
RJ45
RJ45
Transmission rates
100 MBit/s
100 MBit/s
100 MBit/s
Set via
automatic
automatic
automatic
Max. number of STTx
and STRx connections
64
64
64
Max. number of FSTx
and FSRx connections
64
64
64
Cycle time (t_SNp)
2...60 000 ms
2...60 000 ms
2...60 000 ms
Max. number of variables
with elementary ST data
types
5000
5000
5000
Max. number of variables
with elementary FS data
types
4000
4000
4000
Environmental data
312070
314070
315070
Application site
In accordance with the
standard
–
–
EN 501253
Application site
–
–
Track area (1 m 3 m)
In accordance with the
standard
–
–
EN 61373
Application site
–
–
Category 1, Class A + B
Climatic suitability
EN 6006821, EN
60068214, EN
6006822, EN
60068230, EN
60068278
EN 6006821, EN
60068214, EN
6006822, EN
60068230, EN
60068278
EN 50155, EN 6006821,
EN 60068214, EN
6006822, EN
60068230, EN
60068278