7 operation, Messages, 1 display elements for device diagnostics – Pilz PNOZ mmc3p DP User Manual

Page 23: 7operation, 1 messages

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-1

7.1

Messages

7

Operation

7

7000

Operation

Operation

7-

7.1

Messages

7100

Messages

7-

Betrieb_Meldungen_allgemein_BA

When the supply voltage is switched on, the PNOZmulti safety system

copies the configuration from the chip card.

The LEDs "POWER","DIAG", "FAULT", "IFAULT" and "OFAULT" light up

on the base unit.

Betrieb_Meldungen_Feldbus_Profibus

The expansion module PNOZ mmc3p is configured and started auto-

matically. The "ONLINE" and "OFFLINE" LEDs indicate the status of the

PNOZ mmc3p on PROFIBUS-DP.

If the expansion module PNOZ mmc3p does not receive a configuration

from the base unit for a period of 30 s, the expansion module PNOZ

mmc3p connects to PROFIBUS-DP and "ONLINE" status is displayed

on PROFIBUS-DP. The error message "External Error" is sent to the

Master.

7.1.1

Display elements for device diagnostics

Display elements for device diagnostics

7-

Anzeige Legende 3x

Legend:

Betrieb_Anzeige_Feldbus_PROFIBUS-DP_BA

LED on

LED flashes

LED off

LED

Meaning

POWER

Supply voltage is present

Supply voltage is not present

ONLINE

PNOZ mmc3p online, data exchange is possible

Master has sent the telegram "Global Control Clear". Virtual input bits i0 ... i23 are set
to "0"; expanded input bits i24 ... i127 are frozen.

PNOZ mmc3p not online

OFFLINE

PNOZ mmc3p offline, data exchange is not possible

PNOZ mmc3p not offline