6 commissioning, Wiring, 1 general wiring guidelines – Pilz PNOZ mmc3p DP User Manual

Page 19: 2 connecting the supply voltage, 3 profibus-dp-interface, 6commissioning, 1 wiring

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-1

6.1

Wiring

6

Commissioning

6

6000

Commissioning

Commissioning

6-

6.1

Wiring

6100

Wiring

6-

6.1.1

General wiring guidelines

General wiring guidelines

6-

Verdrahtung_multi_Modul

The wiring is defined in the circuit diagram of the PNOZmulti Configura-

tor.

Note:

Information given in the "Technical details" must be followed.

Verdrahtung_Montageschiene mit Schutzerde verbinden

Always connect the mounting rail to the protective earth via an earth-

ing terminal. This will be used to dissipate hazardous voltages in the

case of a fault.

Verdrahtung_Netzteil_sichere_Trennung

The power supply must meet the regulations for extra low voltages

with safe separation.

6.1.2

Connecting the supply voltage

Connecting the supply voltage

6-

Verdrahtung_multi_Feldbus_Versorgungsspannung_Mini

Connect the supply voltage to the fieldbus module:

Terminal 24 V: + 24 V DC

Terminal 0 V: 0 V

6.1.3

PROFIBUS-DP-interface

PROFIBUS DP interface

6-

Verdrahtung

It is possible to define which outputs on the control system will commu-

nicate with PROFIBUS-DP. The connection to PROFIBUS-DP is made

via a female 9-pin D-Sub connector in accordance with the guidelines of

the PROFIBUS User Group (PNO).

n.c. = not connected

Please note the following when connecting to PROFIBUS-DP:

Only use metal plugs or metallised plastic plugs

Twisted pair, screened cable must be used to connect the interfaces

1

5

9

6

1: n.c.

2: n.c.

3: B (RxD/TxD-P)

4: CNTR-P

5: DGND

6: VP

7: n.c.

8: A (RxD/TxD-N)

9: n.c.