5 installation, General installation guidelines, 1 dimensions – Pilz PNOZ mml2p User Manual

Page 17: 5installation, 1 general installation guidelines

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

5-1

5.1

General installation guidelines

5

Installation

5

5000

Installation

Installation

5-

5.1

General installation guidelines

5100

General installation guidelines

5-

Montage_multi_mini_allgemein

The unit should be installed in a control cabinet with a protection type

of at least IP54.

Fit the safety system to a horizontal mounting rail. The venting slots

must face upwards and downwards. Other mounting positions could

destroy the safety system.

Use the notch on the rear of the unit to attach it to a mounting rail.

In environments exposed to heavy vibration, the unit should be

secured using a fixing element (e.g. retaining bracket or end angle).

Push the unit upwards or downwards before lifting it from the

mounting rail.

To comply with EMC requirements, the mounting rail must have a low

impedance connection to the control cabinet housing.

Montage_multi_mini_Temperatur

The ambient temperature of the PNOZmulti units in the control

cabinet must not exceed the figure stated in the technical details,

otherwise air conditioning will be required.

Montage_EMV ESD

5.1.1

Dimensions

Dimensions

5-

Abmessungen PNOZ mml2p

CAUTION!

Damage due to electrostatic discharge!

Electrostatic discharge can damage components. Ensure

against discharge before touching the product, e.g. by touching

an earthed, conductive surface or by wearing an earthed

armband.

120 (4.72")

* 100 (3,94")

98 (3.86")

22,5

(0.88")