Operation, Status indicators, Faults - malfunctions – Pilz PNOZ c2 24VDC 2n/o User Manual

Page 9: Technical details, Faults ­ malfunctions

background image

PNOZ c2

Operating Manual PNOZ c2
22212­EN­02

9

Operation

The unit is ready for operation when the Power LED is permanently lit.

LEDs indicate the status and errors during operation:

Status indicators

Power 
Supply voltage is present.

CH.1 
Safety contacts of channel 1 are closed.

CH.2 
Safety contacts of channel 2 are closed.

Faults ­ malfunctions

}

Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.

Technical details

General

710002

Approvals

CCC, CE, EAC (Eurasian), TÜV, cULus Listed

Electrical data

710002

Supply voltage

Voltage

24 V

Kind

DC

Voltage tolerance

­20 %/+20 %

Output of external power supply (DC)

3,0 W

Residual ripple DC

20 %

Continuous duty

100 %

Max. inrush current impulse

Current pulse, A1

2,00 A

Pulse duration, A1

4,0000 ms

Current pulse, input circuit

0,20 A

Pulse duration, input circuit

70,0 ms

Current pulse, feedback loop

0,15 A

Pulse duration, feedback loop

1,0 ms

Current pulse, start circuit

0,15 A

Pulse duration, start circuit

1,0 ms

Voltage at

Input circuit DC

24,0 V

Start circuit DC

24,0 V

Feedback loop DC

24,0 V