beautypg.com

Safety characteristic data – Pilz PNOZ c2 24VDC 2n/o User Manual

Page 12

background image

PNOZ c2

Operating Manual PNOZ c2
22212­EN­02

12

Mechanical data

710002

Conductor cross section with spring­loaded terminals:
Flexible with/without crimp connector

0,25 ­ 1,50 mm², 24 ­ 16 AWG

Spring­loaded terminals: Terminal points per connec­
tion

1

Stripping length

9 mm

Dimensions

Height

105,0 mm

Width

22,5 mm

Depth

100,0 mm

Weight

160 g

The standards current on 2012­12 apply.

Safety characteristic data

Operating
mode

EN ISO
13849­1:
2008

PL

EN ISO
13849­1:
2008

Category

EN IEC
62061

SIL CL

EN IEC
62061

PFH

D

 [1/h]

IEC 61511

SIL

IEC 61511

PFD

EN ISO
13849­1:
2008

T

M

 [year]

Safety con­
tacts, in­
stantaneous PL e

Cat. 4

SIL CL 3

2,31E­09

SIL 3

2,03E­06

20

INFORMATION

All the units used within a safety function must be considered when determ­
ining the safety characteristic data of the overall system. As well as these
safety characteristic data, the systematic and structural characteristic data
have to be taken into account.

INFORMATION

A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.