Service life graph

The service life graphs indicate the number of cycles from which failures due to wear must
be expected. The wear is mainly caused by the electrical load; the mechanical load is negli­
gible.

Example

}

Inductive load: 0,2 A

}

Utilisation category: AC15

}

Contact service life: 2,000,000 cycles

Provided the application requires fewer than 2,000,000 cycles, the PFH value (see tech­
nical details) can be used in the calculation.

To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With contact­
ors, use freewheel diodes for spark suppression.

Order reference

Type

Features

Terminals

Order no.

PNOZ c1

24 VDC

With spring­loaded terminals

710 001

EC Declaration of Conformity

This product/these products meet the requirements of the directive 2006/42/EC for ma­
chinery of the European Parliament and of the Council. The complete EC Declaration of
Conformity is available on the Internet at www.pilz.com/downloads.
Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix­Wankel­Str. 2, 73760 Ost­