Wiring

Please note:

}

Information given in the "

Technical details [

 9]

" must be followed.

}

The outputs 13­14, 23­24, 33­34 and 43­44 are safety contacts.

}

To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details).

}

Calculation of the max. cable runs l

max 

in the input circuit:

R

lmax

R

l

/ km

I

max

=

R

lmax

 = max. overall cable resistance (see Technical details)

R

l

 / km = cable resistance/km

}

Use copper wire that can withstand 60/75 °C.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in­
ductive loads.

}

Do not switch low currents using contacts that have been used previously with high cur­
rents.

Preparing for operation

Supply voltage

AC

DC

A1

A2

PZE

24 V DC

0 V

Input circuit

Single­channel

Dual­channel

Base unit:
Safety relay PNOZ X

Driven via safety contacts

A1

A2

PZE

24 V DC

0 V

Base unit:
Safety relay PNOZmulti

Driven via semiconductor outputs
(24 VDC)

A1

PZE

A2

0 V

O1

L-

Feedback loop

Base unit: Safety relay PNOZ X Base unit: Safety relay PNOZmulti

Y1, Y2 and Input are inputs on
the base unit; they evaluate the
feedback loop