Block diagram/terminal configuration, Function description, Installation – Pilz PZE X4P 24VDC 4n/o User Manual
Page 6

PZE X4P
Operating Manual PZE X4P
1003201EN08
6
}
Earth fault in the input circuit:
The output relays deenergise and the safety contacts open.
Block diagram/terminal configuration
CH.2
CH.1
PNOZ X4P
P1
13
A1
Y1 Y2 43
24
14
A2
P1
P2
23
14
13
34
33
23
24
33
43
44
34
44
PZE X4P
*
*Insulation between the nonmarked area and the relay contacts: Basic insulation (over
voltage category III), Protective separation (overvoltage category II)
Function description
The contact expansion module is an addon device without delayon deenergisation, and it
is used to expand a safety circuit. The contact expansion module is driven by a base unit
(e. g. emergency stop relay).
}
Functional procedure after closing the safety contacts of the base unit:
–
The supply voltage is present at the input (A1) of the contact expansion module.
–
Close the safety contacts 1314, 2324, 3334 and 4344.
–
The LEDs "CH. 1" and "CH. 2" are lit.
}
Functional procedure after opening the safety contacts of the base unit:
–
There is not supply voltage at input (A1) of the contact expansion module.
–
Open the safety contacts 1314, 2324, 3334 and 4344.
–
The LEDs "CH. 1" and "CH. 2" go out.
Installation
}
The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail.
}
Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele
ment (e.g. retaining bracket or an end angle).
}
If more than 2 units are installed next to each other in the control cabinet, leave a dis
tance of at least 6 mm between the units.