Function description, Installation, Wiring – Pilz PZE X4VP8 24VDC 4n/o User Manual
Page 7

PZE X4VP8
Operating Manual PZE X4VP8
1003206EN06
7
Function description
The contact expansion module is an addon device with selectable delayon deenergisa
tion, and it is used to expand a safety circuit. The contact expansion module is driven by a
base unit (e. g. emergency stop relay).
}
Functional procedure after closing the safety contacts of the base unit:
–
The supply voltage is present at the input (A1) of the contact expansion module.
–
Close the safety contacts 1718, 2728, 3738 and 4748.
–
The LEDs "CH. 1" and "CH. 2" are lit.
}
Functional procedure after opening the safety contacts of the base unit:
–
There is not supply voltage at input (A1) of the contact expansion module.
–
Safety contacts 1718, 2728, 3738 and 4748 open after the delay time.
–
The LEDs "CH. 1" and "CH. 2" go out.
Installation
}
The unit should be installed in a control cabinet with a protection type of at least IP54.
}
Use the notch on the rear of the unit to attach it to a DIN rail.
}
Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele
ment (e.g. retaining bracket or an end angle).
Wiring
Please note:
}
Information given in the "
}
Outputs 1718, 2728, 3738 and 4748 are delayon deenergisation safety contacts.
}
To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details).
}
Calculation of the max. cable runs l
max
in the input circuit:
R
lmax
R
l
/ km
I
max
=
R
lmax
= max. overall cable resistance (see Technical details)
R
l
/ km = cable resistance/km
}
Use copper wire that can withstand 60/75 °C.
}
Sufficient fuse protection must be provided on all output contacts with capacitive and in
ductive loads.
}
Do not switch low currents using contacts that have been used previously with high cur
rents.