PZE X4VP8

Operating Manual PZE X4VP8
1003206­EN­06

7

Function description

The contact expansion module is an add­on device with selectable delay­on de­energisa­
tion, and it is used to expand a safety circuit. The contact expansion module is driven by a
base unit (e. g. emergency stop relay).

}

Functional procedure after closing the safety contacts of the base unit:

The supply voltage is present at the input (A1) of the contact expansion module.

Close the safety contacts 17­18, 27­28, 37­38 and 47­48.

The LEDs "CH. 1" and "CH. 2" are lit.

}

Functional procedure after opening the safety contacts of the base unit:

There is not supply voltage at input (A1) of the contact expansion module.

Safety contacts 17­18, 27­28, 37­38 and 47­48 open after the delay time.

The LEDs "CH. 1" and "CH. 2" go out.

Installation

}

The unit should be installed in a control cabinet with a protection type of at least IP54.

}

Use the notch on the rear of the unit to attach it to a DIN rail.

}

Ensure the unit is mounted securely on a vertical DIN rail (35 mm) by using a fixing ele­
ment (e.g. retaining bracket or an end angle).

Wiring

Please note:

}

Information given in the "

Technical details [

 10]

" must be followed.

}

Outputs 17­18, 27­28, 37­38 and 47­48 are delay­on de­energisation safety contacts.

}

To prevent contact welding, a fuse should be connected before the output contacts (see
Technical details).

}

Calculation of the max. cable runs l

max 

in the input circuit:

R

lmax

R

l

/ km

I

max

=

R

lmax

 = max. overall cable resistance (see Technical details)

R

l

 / km = cable resistance/km

}

Use copper wire that can withstand 60/75 °C.

}

Sufficient fuse protection must be provided on all output contacts with capacitive and in­
ductive loads.

}

Do not switch low currents using contacts that have been used previously with high cur­
rents.