beautypg.com

Safety characteristic data – Pilz PZE X4VP8 24VDC 4n/o User Manual

Page 13

background image

PZE X4VP8

Operating Manual PZE X4VP8
1003206­EN­06

13

Mechanical data

777584

787584

Dimensions

Height

94,0 mm

101,0 mm

Width

45,0 mm

45,0 mm

Depth

121,0 mm

121,0 mm

Weight

320 g

320 g

The standards current on 2009­12 apply.

Safety characteristic data

Operating
mode

EN ISO
13849­1:
2008

PL

EN ISO
13849­1:
2008

Category

EN IEC
62061

SIL CL

EN IEC
62061

PFH

D

 [1/h]

IEC 61511

SIL

IEC 61511

PFD

EN ISO
13849­1:
2008

T

M

 [year]

Safety con­
tacts,
delayed <30
s

PL d

Cat. 3

SIL CL 2

2,48E­09

SIL 2

1,47E­05

20

All the units used within a safety function must be considered when calculating the safety
characteristic data.

INFORMATION

A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.