PZE X4VP8

Operating Manual PZE X4VP8
1003206­EN­06

5

INFORMATION

This gives advice on applications and provides information on special fea­
tures.

Intended use

The unit meets the requirements of EN 60947­5­1, EN 60204­1 and VDE 0113­1. The con­
tact expansion module is used to increase the number of instantaneous safety contacts
available on a base unit. Base units are all safety relays with feedback loop monitoring.

The category that can be achieved in accordance with EN ISO 13849­1 depends on the
category of the base unit. The contact expansion module may not exceed this.

The delay­on de­energisation safety contacts may only be used up to max. PL d (Cat. 3).

For your safety

}

Only install and commission the unit if you have read and understood these operating
instructions and are familiar with the applicable regulations for health and safety at work
and accident prevention.
Ensure VDE and local regulations are met, especially those relating to safety.

}

Any guarantee is rendered invalid if the housing is opened or unauthorised modifica­
tions are carried out.

}

Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120
VDC) are present on the unit, connected control elements and sensors must have a
rated insulation voltage of at least 250 V.

Unit features

}

Positive­guided relay outputs:

4 safety contacts (N/O), delay­on de­energisation

}

LED display for:

Switch status channel 1/2

}

Connection for feedback loop

}

Operation: single­channel

}

Delay­on de­energisation selectable

}

Plug­in connection terminals (either spring­loaded terminal or screw terminal)

}

See order reference for unit types