Pilz PZE X4VP8 24VDC 4n/o User Manual

Page 11

background image

PZE X4VP8

Operating Manual PZE X4VP8
1003206­EN­06

11

Inputs

777584

787584

Number

1

1

Relay outputs

777584

787584

Max. short circuit current IK

1 kA

1 kA

Utilisation category

In accordance with the standard EN 60947­4­1

EN 60947­4­1

Safety­contacts, delayed, AC1
at

240 V

240 V

Min. current

0,01 A

0,01 A

Max. current

5,0 A

5,0 A

Max. power

1200 VA

1200 VA

Safety­contacts, delayed, DC1
at

24 V

24 V

Min. current

0,01 A

0,01 A

Max. current

5,0 A

5,0 A

Max. power

120 W

120 W

Utilisation category

In accordance with the standard EN 60947­5­1

EN 60947­5­1

Safety contacts, delayed AC15
at

230 V

230 V

Max. current

5,0 A

5,0 A

Safety contacts delayed DC13
(6 cycles/min) at

24 V

24 V

Max. current

4,0 A

4,0 A

Utilisation category in accordance
with UL

Voltage

240 V AC G.U. (same polarity)

240 V AC G.U. (same polarity)

With current

6,0 A

6,0 A

Voltage

24 V DC Resistive

24 V DC Resistive

With current

6,0 A

6,0 A

Pilot Duty

B300, R300

B300, R300

Contact fuse protection external,
delayed safety contacts

In accordance with the standard EN 60947­5­1

EN 60947­5­1

Max. melting integral

100 A²s

100 A²s

Blow­out fuse, quick

6 A

6 A

Blow­out fuse, slow

4 A

4 A

Blow­out fuse gG

6 A

6 A

Circuit breaker, 24 V AC/DC,
characteristic B/C

4 A

4 A

Conventional thermal current

5,0 A

5,0 A

Contact material

AgSnO2 + 0,2 µm Au

AgSnO2 + 0,2 µm Au

Times

777584

787584

Delay time tv

5,00 s, 6,00 s, 7,00 s, 8,00 s

5,00 s, 6,00 s, 7,00 s, 8,00 s

Time accuracy

­50 %/+50 %

­50 %/+50 %

Supply interruption before de­ener­
gisation

20 ms

20 ms