7 SERIES 50Hz 700A11 INSTALLATION MANUAL

CAUTION: Do not use rods smaller than 9.5mm

diameter since they may not be strong enough

to support the unit. The rods must be securely

anchored to the ceiling.

General Installation Information cont.

Insulate supply
plenum and use

at least one 90

elbow to

reduce noise

Electrical

Disconnect

Flexible Duct

Collar

Threaded Rods

Line Voltage

Ball V

alves

Hose

Kits

To Line

Power

To

Thermostat

Hanging

Brackets

(Included)

Building Water Loop

O

Figure 2: Horizontal Unit Mounting

Installing Horizontal Units

Remove and discard the compressor hold down shipping

bolt located at the front of the compressor mounting

bracket prior to setting the unit in place. Horizontal units

are available with side or end discharge. Horizontal units

are normally suspended from a ceiling by four or six 9.5mm

diameter threaded rods. The rods are usually attached to

the unit by hanger bracket kits furnished with each unit.

Lay out the threaded rods per the dimensions in Figure

3. Assemble the hangers to the unit as shown. Securely

tighten the brackets to the unit using the weld nuts located

on the underside of the bottom panel. When attaching the

hanger rods to the bracket, a double nut is required since

vibration could loosen a single nut. To allow filter access,

one bracket on the filter side should be installed 180° from

the position shown in Figure 3. The unit should be pitched

approximately 6.35mm towards the drain in both directions

to facilitate the removal of condensate. Use only the bolts

provided in the kit to attach hanger brackets. The use of

longer bolts could damage internal parts.

Some residential applications require the installation of

horizontal units on an attic floor. In this case, the unit

should be set in a full size secondary drain pan on top of a

vibration absorbing pad. The secondary drain pan prevents

possible condensate overflow or water leakage damage to

the ceiling. The secondary drain pan is usually placed on a

plywood base isolated from the ceiling joists by additional

layers of vibration absorbing material.

SPECIAL NOTE: The VS drive is limited to a maximum of

51.7°C ambient temperature. For this reason the 7 Series

is not approved for attic installations. The compressor

compartment temperature is also monitored by the

Aurora. This ‘compressor ambient’ temperature is available

on the AID Tool for reading. The control will de-rate the

compressor when ambient air is above 51.7°C. Installing this

product in an attic could result in loss of warranty.

:STb

@WUVb

!&BV`SORSR

@]RPg]bVS`a

6SfPg]bVS`a

EOaVS`

DWP`ObW]\
7a]ZOb]`

0]ZbO\R
:]QYEOaVS`

1

4

/

/W`1]WZ

2

0

/W`1]WZ

!

"

"

!

Hanger Dimensions

Model

Hanger Kit Part

Number

Unit Hanger Dimensions

A

B

C

D

009

cm.

99S500A03

196.6

70.6

61.2

74.4

012

cm.

99S500A03

196.6

70.6

61.2

74.4

015

cm.

99S500A03

209.3

70.6

61.2

74.4

6/1/12

Weight Distribution

Model

Vertical

Shipping

Weight

Horizontal

Shipping

Weight

Horizontal Weight Distribution

Front

Back

1

2

3

4

009

159.7

175.5

61.2

37.7

39.0

37.7

012

163.8

179.6

65.8

38.1

38.1

37.7

015

174.6

188.2

54.4

54.4

20.4

59.0

Weights are listed in kg

7/18/13

Figure 3: Hanger Location and Assembly