Auxiliary heat ratings, Auxiliary heat electrical data, Electrical data – WaterFurnace 7 Series User Manual
Page 15
15
7 SERIES 50Hz 700A11 INSTALLATION MANUAL
Model
kW
Stages
Min L/s
Model Compatibility
208V
230V
009
012
015
EAL(H)10
7.2
9.6
2
519
•
•
•
EAL(H)15
10.8
14.4
3
590
•
•
•
EAL(H)20
14.4
19.2
4
708
•
•
Air flow level for auxiliary heat (Aux) must be above the minimum air flow in this table
Order the “H” part number when installed on horizontal and vertical rear discharge units
7/17/13
Model
Supply
Circuit
Heater Amps
Min Circuit Amp
Max Fuse (USA)
Max Fuse (CAN)
Max CKT BRK
208 V
240 V
208 V
240 V
208 V
240 V
208 V
240 V
208 V
240 V
EAL(H)10
Single
34.7
40
53.3
60
60
60
60
60
60
60
EAL(H)15
Single
52.0
60
75
85
80
90
80
90
70
100
L1/L2
34.7
40
53.3
60
60
60
60
60
60
60
L3/L4
17.3
20
21.7
25
25
25
25
25
20
30
EAL(H)20
Single
69.3
80
96.7
110
100
110
100
110
100
100
L1/L2
34.7
40
53.3
60
60
60
60
60
60
60
L3/L4
34.7
40
43.3
50
45
50
45
50
40
50
All heaters rated single phase 60 cycle and include unit fan load
All fuses type “D” time delay (or HACR circuit breaker in USA)
6/1/12
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Drive
HWG
Pump
FLA
Ext Loop
FLA
Blower
Motor
FLA
Total Unit
FLA
Minimum
Circuit
Amp
Max Fuse
HACR
Breaker
LRA
CMCC
LRA
Internal
Breaker
009
220-240/50/1
198/264
10.2
18.0
22.0
30.0
0.4
5.4
4.0
31.8
37.3
40
*009
220-240/50/1
198/264
10.2
18.0
22.0
30.0
0.4
5.4
7.0
34.8
40.3
45
012
220-240/50/1
198/264
12.0
23.5
28.0
35.0
0.4
5.4
7.0
40.8
47.8
50
015
220-240/50/1
198/264
12.0
30.0
33.0
40.0
0.4
5.4
7.0
45.8
54.1
60
*With optional 1 hp Variable Speed ECM Motor
Rated Voltage of 220-240/50/1
HACR circuit breaker in USA only
All fuses Class RK-5
5/08/13
Auxiliary Heat Ratings
Auxiliary Heat Electrical Data
Electrical Data