Auxiliary heat ratings, Auxiliary heat electrical data, Electrical data – WaterFurnace 7 Series User Manual

Page 15

background image

15

7 SERIES 50Hz 700A11 INSTALLATION MANUAL

Model

kW

Stages

Min L/s

Model Compatibility

208V

230V

009

012

015

EAL(H)10

7.2

9.6

2

519

EAL(H)15

10.8

14.4

3

590

EAL(H)20

14.4

19.2

4

708

Air flow level for auxiliary heat (Aux) must be above the minimum air flow in this table
Order the “H” part number when installed on horizontal and vertical rear discharge units

7/17/13

Model

Supply

Circuit

Heater Amps

Min Circuit Amp

Max Fuse (USA)

Max Fuse (CAN)

Max CKT BRK

208 V

240 V

208 V

240 V

208 V

240 V

208 V

240 V

208 V

240 V

EAL(H)10

Single

34.7

40

53.3

60

60

60

60

60

60

60

EAL(H)15

Single

52.0

60

75

85

80

90

80

90

70

100

L1/L2

34.7

40

53.3

60

60

60

60

60

60

60

L3/L4

17.3

20

21.7

25

25

25

25

25

20

30

EAL(H)20

Single

69.3

80

96.7

110

100

110

100

110

100

100

L1/L2

34.7

40

53.3

60

60

60

60

60

60

60

L3/L4

34.7

40

43.3

50

45

50

45

50

40

50

All heaters rated single phase 60 cycle and include unit fan load
All fuses type “D” time delay (or HACR circuit breaker in USA)

6/1/12

Model

Rated

Voltage

Voltage

Min/Max

Compressor

Drive

HWG

Pump

FLA

Ext Loop

FLA

Blower

Motor

FLA

Total Unit

FLA

Minimum

Circuit

Amp

Max Fuse

HACR

Breaker

LRA

CMCC

LRA

Internal
Breaker

009

220-240/50/1

198/264

10.2

18.0

22.0

30.0

0.4

5.4

4.0

31.8

37.3

40

*009

220-240/50/1

198/264

10.2

18.0

22.0

30.0

0.4

5.4

7.0

34.8

40.3

45

012

220-240/50/1

198/264

12.0

23.5

28.0

35.0

0.4

5.4

7.0

40.8

47.8

50

015

220-240/50/1

198/264

12.0

30.0

33.0

40.0

0.4

5.4

7.0

45.8

54.1

60

*With optional 1 hp Variable Speed ECM Motor
Rated Voltage of 220-240/50/1
HACR circuit breaker in USA only
All fuses Class RK-5

5/08/13

Auxiliary Heat Ratings

Auxiliary Heat Electrical Data

Electrical Data