7 SERIES 50Hz 700A11 INSTALLATION MANUAL

General

Be sure the available power is the same voltage and phase

as that shown on the unit serial plate. Line and low voltage

wiring must be done in accordance with local codes or

the National Electric Code, whichever is applicable. The

compressor has no internal overload. The circuit breaker in

the control box is the overload protection for the drive and

the compressor. Bypassing the circuit breaker could result

in damage to the compressor and voiding the warranty.

Unit Power Connection

Connect the incoming line voltage wires to L1 and L2 of

the contactor as shown in Figure 13c for single-phase unit.

Consult the Unit Electrical Data in this manual for correct

fuse sizes.

Open lower front access panel. Remove ground fastener

from bottom of control box (Figure 13b). Swing open

control box (Figure 13a). Insert power wires through

knockouts on lower left side of cabinet. Route wires

through left side of control box and connect to contactor

and ground (Figure 13c). Close control box and replace

grounding fastener before unit startup.

Ground Fastener

must be installed for

proper unit ground

Wire Insert

Location

Figure 13c:

Line Voltage 220-240/50/1 control box

Figure 13b:

Wire access (control box closed)

Figure 13a:

Wire access (control box open)

Electrical Connections

Accessory Relay

A set of “dry” contacts has been provided to control

accessory devices, such as water solenoid valves on open

loop installations, electronic air cleaners, humidifiers, etc.

This relay contact should be used only with 24 volt signals

and not line voltage power. The relay has both normally

open and normally closed contacts and can operate with

either the blower or the compressor. Use DIP switch SW2-4

and 5 to cycle the relay with blower, compressor, or control

a slow opening water valve. The relay contacts are available

on terminals #2 and #3 of P2.

A second configurable accessory relay is provided on the

AXB board. When powering high VA draw components

such as electronic air cleaners or VM type open loop water

valves, R should be taken ‘pre-fuse’ from the ‘R’ quick

connect on the ABC board and not the ‘post-fuse’ ‘R’

terminal on the thermostat connection. If not, blown ABC

fuses might result.

220 Volt Operation

All 220-240 units are factory wired for 240 volt operation.

For 220 volt operation, the red and blue transformer wires

must be switched on terminal strip PS.

L1

L2

PB1

CB

L1

L2

Compressor

Drive

Overload

CAUTION: Frequent cycling of power to the drive

can damage the drive! Wait at least 5 minutes

between cycles (connecting and disconnecting

power to the drive).