beautypg.com

Spectrum Controls 140 ACI 051 00sc User Manual

Page 51

background image

Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc

44

STEP 3: Check the module’s fault LED.

VERIFY: The module’s red FAULT LED is off. This LED indicates a
module hardware error.

CORRECTIVE ACTION:

The module has a fatal hardware error. Contact your local distributor
or Spectrum Controls Customer Satisfaction Group listed at the back
of this manual.

The module has a front LED panel that includes 35 LEDs:

Ready LED -

1 Green LED indicates module’s self test has passed and is ready to
communicate.

Active LED -

1 Green LED indicates BUS communication is established between the
module the rack.

Fault LED -

1 Red LED indicates a module self test error, or fatal H/W error. A blink
code will be defined that will indicate the type of self test error. Count
the number of blinks before a pause to determine the error code in the
table below.

Fault LED Blink Code

Blink #

Fault

3

DPM Test Error

4

CPU Error

5

Watchdog Timer Error

6

RAM Error

7

Flash EPROM CRC Error

8

Calibration EEPROM Error

Channel LED -
32 Green LEDs indicates the channel is enabled and a valid input signal
level is present. The LED is off if the channel is disabled. A blinking
LED indicates that the channel has exceeded a range limit.