Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
40
6.3 Demultiplexing Channel Data - Manual Mode
Manual mode allows deterministic data acquisition. You may specify the
specific group of data you would like to acquire as opposed to the
Autosequence Mode which cycles through data blocks. Manual mode
requires that the Autosequence Mode be disabled; Bit 10 = 1.
The following ladder logic shows how to move data from the 8 multi-
plexed input words to a block of 32 output words starting at location
400101 with the manual mode. This example file for use only with
Modsoft programming software can be formed on the install disk shipped
with your module. The file is under the A:\Programs subdirectory. To
install:
1. Insert the install disk into drive A:
2. Copy A:\Programs\QAI32_GI.* C:\Modsoft\Programs
3. Select File QAI32_GI under Modsoft to run.
The I/O map is as follows: (Manual Mode)