Chapter 4 module configuration and status, 1 configuration word format (register 4x), 4x group channel disable: bits 1-8 – Spectrum Controls 140 ACI 051 00sc User Manual
Page 28
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
23
Chapter 4
MODULE CONFIGURATION AND STATUS
The 140 AxI 05x 00sc uses a total of nine 3x level and one 4x level
registers. After Modsoft (Section 2.3) or Concept (Section 3.3) soft-
ware is installed, additional configuration and status registers are set as
follows:
4.1
Configuration word format (Register 4x)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Select a group
Mode Select
Autosequence Disable
Reserved
Disable channel 1-4
Disable channel 5-8
Disable channel 9-12
Disable channel 13-16
Disable channel 17-20
Disable channel 21-24
Disable channel 25-28
Disable channel 29-32
4x Group Channel Disable: Bits 1-8
These bits are used to fine tune the response time of your system. They
enable data acquisition on eight groups of four channels each. A “0”
enables the group, a “1” disables the group. Disabling groups of chan-
nels improves system response time.