Spectrum Controls 140 ACI 051 00sc User Manual
Page 19
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
14
3.4
Concept I/O Map Module Parameters:
Concept programming software does not implement zoom screens for
ModConnect partner modules and allows only direct editing of the I/O
configuration parameters using 16 bit hex values.
From the Concept main screen, highlight the “configure” pull-down menu
and choose “I/O Map.” In the I/O Map screen insert the number for the
correct “drop” and choose “edit.” Select the Spectrum Controls catalog
number that you wish to use from the list presented. When the screen
appears, representing the Spectrum module you have selected, highlight
the parameters button. You must insert Hex values for registers #1, 2
and 3 to fully configure the module. The format that will instruct you on
how to create the I/O map parameters is listed below. For each of the
parameters listed we have provided a detailed explanation in Chapter 2.
Please refer to detailed functional descriptions in the MODSOFT zoom
screen discussions (Section 2.4). You must go through each of the
options below to establish the correct pattern for each of these three
registers. Once you have the bit pattern, then you can convert each to a
four-digit Hex value that is used in the parameters screen.