beautypg.com

Spectrum Controls 1769sc-HART Modules User Manual

Page 32

background image

Compact IO™ Isolated HART Analog Input Module

User's Manual 0300215-03 Rev. A

4-4

4.

This screen is used to narrow your search for I/O modules to configure into your
system. With the initial release of the CompactLogix5320 controller, this screen
only includes the “Generic 1769 Module”. Click the OK button and the
following default Generic Profile screen appears:

Figure 4-5

5.

First, select the Comm Format (“Data – INT” for the 1769sc-IF4IH), then fill in
the name field. For this example, “IF4IH” is used to help identify the module
type in the Controller Organizer. The Description field is optional and may be
used to provide more details concerning this I/O module in your application.

The slot number must be selected next, although it will begin with the first
available slot number, 1, and increments automatically for each subsequent
Generic Profile you configure. For this example, the 1769sc-IF4IH HART
module is located in slot 1.

The Comm Format, Assembly Instance and Size values are listed in the
following table for the 1769sc-IF4IH HART module:

Table 4-1 (Generic Profile Parameters)

1769 I/O

Module

Comm

Format

Parameter

Assembly

Instance

Size

(16-Bit)

IF4IH Data-INT Input

Output

Config

101

100

102

72

46

34

6.

Enter the Assembly Instance numbers and their associated sizes for the 1769sc-
IF4IH module into the Generic Profile. When complete, the Generic Profile for a
1769sc-IF4IH module should look like the following: