Spectrum Controls 1769sc-HART Modules User Manual
Page 174
Compact IO™ Isolated HART Analog Input Module
User's Manual 0300215-03 Rev. A
A-2
Specification Description
Minimum Update Time
10 ms with 360 Hz filter
Maximum Update Time
108 ms with 28.5 Hz filter
Isolation
Channel to Rack
710 VDC or 500 VAC for one minute. Optical &
magnetic
Channel to Channel
710 VDC or 500 VAC for one minute. Optical &
magnetic
PCB spacing
0.033in. (0.85mm)
Isolation spacing requirements
PCB spacing
Non-PCB spacing
Through Air
Over Surface
0.033in. (0.85mm)
0.063in (1.59mm)
0.063in (1.7mm)
Input Protection
Voltage Terminal: +/- 24VDC continuous
Current Terminal: +/-28mA continuous, +/- 7 VDC
Power Requirements
Internal rack +5V
175 mA
Internal rack +24V
60 mA
Fusing None
Section A.2
Environmental
Specifications
Test Description
Standard
Class/Limit
Vibration/Shock
Unpack
Shock & Vibration (op)
IEC 600 68-2-6 FC
ICCG-ES #001 A.
Class III
Free Fall Unpackaged
(non-op)
IEC 600 68-2-32#1
Shock Unpackaged (op)
IEC 600 68-2-
27Ea
ICCG-ES #002 A.
Class III, Cat. I
Packaging Tests
NSTA
Will test new packaging
Temperature
0 to 60 Degree C
Temp Cycle (op)
IEC 600 68-2-
14Nb
ICCG-ES #006 C.
0 to +60 2 cycles .5hr/cycle
Thermal mapping of hot
comp
done at 60 deg C, full load
Storage Temperature
-40 to 85 Degree C
High temp (non-op)
IEC 600 68-2-2Bb
ICCG-ES #006 C.
+85 for 16hrs
Low temp (non-op)
IEC 600 68-2-2Ab
ICCG-ES #006 C.
-40 for 16hrs