beautypg.com

Spectrum Controls 1769sc-HART Modules User Manual

Page 10

background image

Compact™ IO Isolated HART Analog Input Module



User's Manual 0300215-03 Rev. A

1-2

Section 1.3
Filter
Frequencies

The module uses a digital filter that provides high frequency noise rejection for the input
signals. The filter is programmable, allowing you to select from five different filter
frequencies for each channel:

28.5 Hz

50 Hz

60 Hz

300 Hz

360 Hz

Section 1.4
Hardware
Features

The module contains a removable terminal block. Channels are wired as differential
inputs (i.e. each channel will have a dedicated ground).

Note: A jumper must be installed on the terminal block between CH- and CH-iRtn for
all current input ranges.

Module configuration is done via the controller’s programming software. In addition,
some controllers support configuration via the user program. In either case, the module
configuration is stored in the memory of the controller. Refer to your controller’s user
manual for more information. The illustration below shows the module’s hardware
features.


Figure 1-1

5a

9

5b

6

7a

7b

8b

7b

8a

7a

OK

HART

10a

10b

4

10

2b

3

2a

1

DANGER

Do Not Remove RTB Under

Power Unless Area is Non-

Hazardous

Ensure Adjacent Bus
Lever is Unlatched/
Latched Before/After
Removing/Inserting
Module

OK

HART

Item

Description

1

bus lever

2a

upper panel mounting tab

2b

lower panel mounting tab

3

module status LED

4

module door with terminal identification label