Table 9-4 (Extended Fault Codes)
Error Type
Hex Equivalent
Module Error Code
Extended Error I nform ation
Code
Er ror Description
No error
X000
000
0 0000 0000
No error
X216
001
0 0001 0110
Watchdog res et error
X220
001
0 0010 0000
Critical code failure
X221
001
0 0010 0001
Failed calibration/critic al EEPROM failure
X403
010
0 0000 0011
Illegal RTS value
X404
010
0 0000 0100
Channel 0 illegal f ilt er configuration
X405
010
0 0000 0101
Channel 1 illegal f ilt er configuration
X406
010
0 0000 0110
Channel 2 illegal f ilt er configuration
X407
010
0 0000 0111
Channel 3 illegal f ilt er configuration
X408
010
0 0000 1000
Channel 0 illegal input range
X409
010
0 0000 1001
Channel 1 illegal input range
X40A
010
0 0000 1010
Channel 2 illegal input range
X40B
010
0 0000 1011
Channel 3 illegal input range
X40C
010
0 0000 1100
Channel 0 illegal data format
X40D
010
0 0000 1101
Channel 1 illegal data format
X40E
010
0 0000 1110
Channel 2 illegal data format
X40F
010
0 0000 1111
Channel 3 illegal data format
X410
010
0 0001 0000
Channel 0 illegal low alarm s etpoint
X411
010
0 0001 0001
Channel 1 illegal low alarm s etpoint
X412
010
0 0001 0010
Channel 2 illegal low alarm s etpoint
X413
010
0 0001 0011
Channel 3 illegal low alarm s etpoint
X414
010
0 0001 0100
Channel 0 illegal high alarm setpoint
X415
010
0 0001 0101
Channel 1 illegal high alarm setpoint
X416
010
0 0001 0110
Channel 2 illegal high alarm setpoint
X417
010
0 0001 0111
Channel 3 illegal high alarm setpoint
X418
010
0 0001 1000
Channel 0 illegal alarm deadband
X419
010
0 0001 1001
Channel 1 illegal alarm deadband
X41A
010
0 0001 1010
Channel 2 illegal alarm deadband
X41B
010
0 0001 1011
Channel 3 illegal alarm deadband
X41C
010
0 0001 1100
Ch0 Process alarm values set when alarms are disabled
X41D
010
0 0001 1101
Ch1 Process alarm values set when alarms are disabled
X41E
010
0 0001 1110
Ch2 Process alarm values set when alarms are disabled
X41F
010
0 0001 1111
Ch3 Process alarm values set when alarms are disabled
X420
010
0 0010 0000
Illegal pass-through scheme selected
Hardware-
Spec if ic Error
Module-Specific
Configuration
Error
Section 9.8
Module
Inhibit Function
Some controllers support the module inhibit function. See your controller manual for
details.
Whenever the 1769sc-IF4IH module is inhibited, the module continues to provide
information about changes at its inputs to the 1769 CompactBus master (for example, a
CompactLogix controller).