Abnormal, Description & checkpoint, Solution – OPTI-UPS DS160KD33 User Manual

Page 80: 6) fans cannot work while ups is on, Replace the fuses or install them well, Abnormal voltage output in r phase, 7) the rectifier shunt down and high dc led lit up, 3c pcb has problem, 8) abnormal voltage in reserve, Fuse has blown in 3a pcb

background image

9-3


Abnormal

Description & Checkpoint

Solution

(6) Fans cannot
work while
UPS is on.

The fuses positioned behind PCB holder
have been blown or are not installed well.

Replace the fuses or install
them well.

Abnormal voltage output in R phase.

Refer to PCB LED
Detecting Guide and check
the 3T PCB of R phase.

(7) The
rectifier shunt
down and
HIGH DC LED
lit up.

Voltage limit function failure in the 3B,
which contributes to the DC voltage
becomes over 430V.

Refer to PCB LED
Detecting Guide and check
the 3B PCB.

3C PCB has problem.

Refer to PCB LED
Detecting Guide and check
the 3C PCB.

(8) Abnormal
voltage in
reserve.

RESERVE AC FAIL LED lights up. LCD
menu also displays the abnormal voltage
in reserve. (REAL TIME DATA menu

RESERVE DATA menu).

Check the reserve wiring
and connect with the right
source.

Fuse has blown in 3A PCB

Replace the fuse.

If the abnormal cannot be improved as the
aforesaid solution action has been taken.

Refer to PCB LED
Detecting Guide and check
the 3A PCB.

(9) Abnormal
frequency in
reserve.

RESERVE FREQ FAIL LED lights up.
LCD menu also displays the abnormal
voltage in reserve. (REAL TIME DATA
menu

→ RESERVE DATA menu).

Check the reserve wiring
and connect with the right
source.

Fuse has blown in 3A PCB

Replace the fuse.

If the abnormal cannot be improved as the
aforesaid solution action has been taken.

Refer to PCB LED
Detecting Guide and check
the 3A PCB.