3.3. Cable Selection

The following tables list all the information between KVA of the UPS and the size
and rating of the cables. Inadequate cable size or over sized breaker will incur risk
of fire or damage of insulation. Therefore, please look up the following tables to
determine the input circuit breaker rating and the size of cable for input, output and
battery connections. These data are for reference; final decision should be made in
accordance with the local electrical regulations.

BREAKER RATING FOR INPUT

KVA

INPUT

Imax(A)

NFB(A)

20

230/400V 3

Φ

50

50

30

230/400V 3

Φ

73

75

40

230/400V 3

Φ

98

100

50

230/400V 3

Φ

122

125

60

230/400V 3

Φ

147

150

80

230/400V 3

Φ

172

175

100

230/400V 3

Φ

215

225

120

230/400V 3

Φ

258

300

160

230/400V 3

Φ

344

350

240

230/400V 3

Φ

520

500

320

230/400V 3

Φ

692

700



CABLE SIZE FOR INPUT

KVA

INPUT

In(A)

R/S/T(mm

2

)

N(mm

2

)

20

230/400V 3

Φ

36

8

14

30

230/400V 3

Φ

54

14

22

40

230/400V 3

Φ

72

22

30

50

230/400V 3

Φ

90

30

38

60

230/400V 3

Φ

108

38

50