6-2

RELAY

CNR15



FAULT – Short when UPS encounter fault condition such as high dc shutdown,

short circuit, fuse/over-heat, overload shutdown, emergent stop, inverter
abnormal, bypass on shutdown, and is latched until manual reset (off
switch) or 30 sec. after fault condition removal

SS – Short when the inverter static switch is conducting, open when reserve

static switch is conducting (The two static switches will never conduct
simultaneously).

BYPASS – Short when the maintenance bypass breaker is closed; open when

the breaker is opened.

BACK-UP – Short when the inverter (running) is back-up by the battery.

BATL – Short when the inverter is consuming the battery and the battery is

about to be exhausted.

COM – This contact is the OR result of the signals described above. That is,

any other contact close, this contact will close too. The signal to be ored is
selectable through SWR2. See the figure



SWR2-1

SWR2-2

RELAY

CNR12

INVON





TO

INTERNL

CIRCUIT

SWR2-3

SWR2-4

SWR2-5

SWR2-6

SWR2-7



OR

















SWR2-8

RELAY

CNR17

RELAY

CNR13

RELAY

CNR16

RELAY

CNR14

RELAY

CNR19

RELAY

CNR20

OVL

FAULT

SS

BYPASS

BACK-

UP BATL

COM