Technical specification – OPTI-UPS DS160KD33 User Manual

Page 29

background image

2-1


2.

TECHNICAL SPECIFICATION

2.1. 20KVA ~ 60KVA UPS 3-Phase Input / 3-Phase Output

TECHNICAL SPECIFICATION

KVA

20

30

40

50

60

RECTIFIER

INPUT VOLTAGE

220V

∆ / 380V∆ / 460V∆, 208VY /

380VY / 400VY / 415VY

INPUT RANGE

307 – 520V

INPUT FREQUENCY

50 / 60 Hz +/- 7%

INPUT POWER FACTOR

0.8

NORMAL INPUT CURRENT(A)

36

54

72

90

108

MAXIMUM INPUT CURRENT(A)

45

68

90

113

136

POWER WALK IN

0% - 100% : 20 sec

EFFICIENCY

99%

VOLTAGE REGULATION

1%

CURRENT LIMIT(A)

54

81

108

135

162

RIPPLE VOLTAGE

0.5%

BATTERY

BATTERY TYPE

SEAL LEAD ACID / NiCd

NO. OF CELLS

174 / 271

VOLTAGE RANGE

295 – 410VDC / 285-415VDC

MAXIMUM CHARGE
CURRENT (ADC)

10

15

20

25

30

BATTERY LOW VOLTAGE

320VDC / 305VDC

BATTERY LOW STOP VOLTAGE

295VDC / 285VDC

BOOST CHARGE

410VDC / 415VDC

FLOAT CHARGE

396VDC / 410VDC