2-5
KVA
80
100
120
160
INVERTER
DC INPUT RANGE
285 – 415VDC
WAVE FORM
SINUSOID
OUTPUT VOLTAGE
208 / 380 / 400 / 415 VY 3 PHASE
WITH NEUTRAL
OUTPUT POWER FACTOR
0.8
VOLTAGE REGULATION
100% UNBALANCE LOAD
+ / - 1 %
FREQUENCY LOCK RANGE
45 – 55 Hz / 55 – 65 Hz
OUTPUT FREQUENCY
(FREE RUNNING)
50 / 60 Hz + / - 0.1 Hz
PHASE SHIFT UNDER
100% UNBALANCE LOAD
120 % + / - 0.5
∘
THD (LINEAR LOAD)
< 2 %
OVERLOAD
- <110%
CONTINUOUS
- 110 – 125%
15 min
- 125 – 150%
10min
- > 150%
60 sec
EFFICIENCY (100% LOAD)
94.5%
94.5%
95%
95%
MAXIMUM OUTPUT
PEAK CURRENT(A)
348
432
520
693
STATIC SWITCH
VOLTAGE RANGE
173 – 277 VAC (LINE TO NEUTRAL)
FREQUENCY RANGE
45 – 55 Hz / 55 – 65 Hz
EFFICIENCY
99.5%
TRANSFER TIME:
- MAINS -> INVERTER
0 ms
- INVERTER -> MAINS
0 ms
OVERLOAD
- 100%
30 sec
- 300%
1 sec
ISOLATION WITH OUTPUT
YES