2-4



2.2. 80KVA ~ 160KVA UPS 3-Phase Input / 3-Phase Output

TECHNICAL SPECIFICATION

KVA

80

100

120

160

RECTIFIER

INPUT VOLTAGE

220V

∆ / 380V∆ / 460V∆, 208VY /

380VY / 400VY / 415VY

INPUT RANGE

307 – 520V

INPUT FREQUENCY

50 / 60 Hz +/- 7%

INPUT POWER FACTOR

0.8

NORMAL INPUT CURRENT(A)

144

180

216

288

MAXIMUM INPUT CURRENT(A)

180

225

270

360

POWER WALK IN

0% - 100% : 20 sec

EFFICIENCY

99%

VOLTAGE REGULATION

1%

CURRENT LIMIT(A)

216

270

324

432

RIPPLE VOLTAGE

0.5%

BATTERY

BATTERY TYPE

SEAL LEAD ACID / NiCd

NO. OF CELLS

174 / 271

VOLTAGE RANGE

295 – 410VDC / 285-415VDC

MAXIMUM CHARGE
CURRENT (ADC)

40

50

60

80

BATTERY LOW VOLTAGE

320VDC / 305VDC

BATTERY LOW STOP VOLTAGE

295VDC / 285VDC

BOOST CHARGE

410VDC / 415VDC

FLOAT CHARGE

396VDC / 410VDC