Interface connections, Dry contacts, Ovl – short whenever ups is overloaded – OPTI-UPS DS160KD33 User Manual

Page 68

background image

6-1

6.

INTERFACE CONNECTIONS

All interfaces are connected from 3R PCB. See the figure as below.









6.1. Dry Contacts

8 terminals of dry contact are provided. These terminals are normal open, when
event happens the terminal will conduct. Maximum contact rating is
16A/250VAC(16A/30VDC). They are:

INVON – Short whenever inverter is on, open when inverter is off.

OVL – Short whenever UPS is overloaded.