OPTI-UPS DS160KD33 User Manual
Page 39
2-11
KVA
200
240
300
320
INVERTER
DC INPUT RANGE
285 – 415VDC
WAVE FORM
SINUSOID
OUTPUT VOLTAGE
380 / 400 / 415 V 3 PHASE WITH
NEUTRAL
OUTPUT POWER FACTOR
0.8
VOLTAGE REGULATION
0-100% LOAD
+ / - 1 %
FREQUENCY LOCK RANGE
45 – 55 Hz / 55 – 65 Hz
OUTPUT FREQUENCY
(FREE RUNNING)
50 / 60 Hz + / - 0.1 Hz
PHASE DIFFERENCE WITH
RESERVE INPUT
120°+ / - 0.5°
THD (LINEAR LOAD)
< 5 %
OVERLOAD
- <110%
CONTINUOUS
- 110 – 125%
15 min
- 125 – 150%
10 min
- > 150%
60 sec
EFFICIENCY(100% LOAD)
95%
95%
95%
95%
MAXIMUM OUTPUT
PEAK CURRENT(A)
800
1000
1250
1300
STATIC SWITCH
VOLTAGE RANGE
173 – 277 VAC (LINE TO NEUTRAL)
FREQUENCY RANGE
45 – 55 Hz / 55 – 65 Hz
EFFICIENCY
99.5%
TRANSFER TIME:
- MAINS -> INVERTER
0 ms
- INVERTER -> MAINS
0 ms
OVERLOAD
- 100%
30 sec
- 300%
1 sec
ISOLATION WITH OUTPUT
YES