beautypg.com

OPTI-UPS DS160KD33 User Manual

Page 30

background image

2-2



KVA

20

30

40

50

60

INVERTER

DC INPUT RANGE

285 – 415VDC

WAVE FORM

SINUSOID

OUTPUT VOLTAGE

208 / 380 / 400 / 415 VY 3 PHASE

WITH NEUTRAL

OUTPUT POWER FACTOR

0.8

VOLTAGE REGULATION 100%
UNBALANCE LOAD

+ / - 1 %

FREQUENCY LOCK RANGE

45 – 55 Hz / 55 – 65 Hz

OUTPUT FREQUENCY
(FREE RUNNING)

50 / 60 Hz + / - 0.1 Hz

PHASE SHIFT UNDER
100% UNBALANCE LOAD

120 % + / - 0.5

THD (LINEAR LOAD)

< 2 %


OVERLOAD

- <110%

CONTINUOUS

- 110 – 125%

15 min

- 125 – 150%

10 min

- > 150%

60 sec

EFFICIENCY (100% LOAD)

93%

93%

93.5%

93.5%

94%

MAXIMUM OUTPUT
PEAK CURRENT(A)

87

130

174

218

260

STATIC SWITCH

VOLTAGE RANGE

173 – 277 VAC (LINE TO NEUTRAL)

FREQUENCY RANGE

45 – 55 Hz / 55 – 65 Hz

EFFICIENCY

99.5%

TRANSFER TIME:

- MAINS -> INVERTER

0 ms

- INVERTER -> MAINS

0 ms

OVERLOAD

- 100%

30 sec

- 300%

1 sec

ISOLATION WITH OUTPUT

YES