OPTI-UPS DS160KD33 User Manual
Page 54
![background image](/manuals/740052/54/background.png)
4-5
(c) Close the rectifier breaker - The rectifier will be automatically started if the
power source connected is correct. The DC voltage will slowly
rise up (15 – 30sec.) until the designated voltage is reached, and
will keep the value anyhow. Now, the DC is already ready for the
inverter.
(d) Close the battery breaker - A fuse holder is employed in the battery to the
DC bus for safety purpose. Now the batteries will take-over to
supply the DC bus if rectifier mains fail.
(e) Push inverter on switch – To on the inverter, the inverter on switch and the
control switch must be pressed simultaneously. The inverter will
start working and inverter output will be established in 4 sec. The
load will be automatically transferred to the inverter 3 sec. later.
Now the UPS comes again into normal operation now.