2-8


KVA

20

30

40

50

INVERTER

DC INPUT RANGE

285 – 415VDC

WAVE FORM

SINUSOID

OUTPUT VOLTAGE

220 / 230 / 240 V, 1p2w or 1p3w

OUTPUT POWER FACTOR

0.8

VOLTAGE REGULATION
0-100% LOAD

+ / - 1 %

FREQUENCY LOCK RANGE

45 – 55 Hz / 55 – 65 Hz

OUTPUT FREQUENCY
(FREE RUNNING)

50 / 60 Hz + / - 0.1 Hz

PHASE DIFFERENCE WITH
RESERVE INPUT

+ / - 0.5

THD (LINEAR LOAD)

< 2 %


OVERLOAD

- <110%

CONTINUOUS

- 110 – 125%

15 min

- 125 – 150%

10 min

- > 150%

60 sec

EFFICIENCY (100% LOAD)

93%

93%

93.5%

93.5

MAXIMUM OUTPUT
PEAK CURRENT(A)

260

390

520

650

STATIC SWITCH

VOLTAGE RANGE

173 – 277 VAC (LINE TO

FREQUENCY RANGE

45 – 55 Hz / 55 – 65 Hz

EFFICIENCY

99.5%

TRANSFER TIME:

- MAINS -> INVERTER

0 ms

- INVERTER -> MAINS

0 ms

OVERLOAD

- 100%

30 sec

- 300%

1 sec

ISOLATION WITH OUTPUT

YES