1-22


BAT LOW – the LED will lit as long as the DC voltage is lower than

320VDC.

BAT LOW STOP – the LED will lit as long as the DC voltage is lower than

295VDC, inverter on is prohibited.

FAULT – the inverter is shutdown due to abnormal conditions such as

overload, short circuit, high DC, fuse over temperature, bypass breaker on
or emergent stop.

Since these LEDs are located behind the transparent window, the user can see
them clearly without opening the door.

D: Buzzer outlet: The buzzer is located inside the PCB holder; therefore, a hole is

opened to let the beep sound can be heard outside. Usually, the user should not be
expected to watch the UPS all the time, therefore when abnormal conditions
happen audible sound should be emitted to warn the user come over to check
what happens to the UPS. The buzzer will beep under either one of the following
conditions:

INVERTER IS OVERLOADED-

>110%, beep once / 3 seconds

>125%, beep once / second

>150%, beep twice / second

BACK- UP

>320VDC, beep once / 3 seconds

<320VDC, beep twice / second

<295VDC, no beeping

INVERTER IS SHORT CIRCUITED - beep continuously

FUSE BROKEN - beep continuously

HEAT SINK OVER TEMPERATURE - beep continuously

HIGH DC SHUTDOWN - beep continuously

BYPASS ON STOP - beep continuously