3-2
(e) It is necessary to guarantee the temperature and humidity values of the site
into which the UPS will be installed should be within the range allowed by the
specification. The UPS is capable of continuous normal operation within a
temperature range of 0℃(32℉) to 40℃(104℉). For optimal performance and
reliability to prolong UPS’s lifetime, it is recommended to keep the environment
temperature below 25℃, and humidity below 80%.
(f) If the UPS is installed outdoor, avoid direct exposure of the UPS to the
sunlight and rain. Avoid direct confrontation with sand, dust or wind.
(g) The floor loading capacity should be big enough to endure the weight of the
UPS. Four tough right angled steel foot stands are attached with the UPS, please
insert the corresponding screw nut (dia.1/2”) into the floor for securing the UPS
on the floor when it is locate on territory where earthquake is expected or
moving vehicle, or tanker etc. Dimensions of the 1/2” nut on the to secure the
UPS are shown below.